An inhibited heat transfer fluid which is designed to protect all solar thermal heating systems at elevated temperatures. This product is effective both in the gaseous and liquid state at temperatures in excess of 356 °F (180 °C).
Solar S1 provides corrosion inhibition to all metals commonly found in solar thermal systems. Solar S1 is compatible with all non-metallics commonly found in solar thermal systems. It is ready to use and should not be mixed with other heat traNSF CIASer fluids or diluted with water or glycol. If other heat traNSF CIASer fluids have been previously used, drain the system completely and rinse with Solar S1 before filling.
Solar S1 is suitable for use in solar applications with stagnation temperatures in excess of 680°F (360°C) provided that the solar thermal system is correctly installed and dimensioned to allow the Fernox Solar S1 to withdraw completely through vaporization from the collectors when the maximum static temperature is reached. Solar S1 should not be exposed to temperatures of 356°F (180°C) or higher for prolonged periods. Temperatures in excess of 392°F (200°C) causes slow degradation of the fluid which can lead to a reduction in product life.
An aqueous solution of monopropylene glycol, and specifically formulated high temperature inhibitors
Appearance: Orange liquid
SG @ 68°F/20°C: 1.035
Refractive Index: 1.381-1.385
pH: 9.4 – 10.3
Alkalinity: 6,300 – 6,500 ppm as CaCO3
Viscosity (68°F/20°C): 8.5 – 8.7 cPs (Brookfield 100 rpm)
Boiling point: 215.6°F – 221°F (102°C – 105°C)
Flash point: None
Water content: 55 – 58%
Freezing point: -18.4°F (-28°C)
Fernox Solar S1 is supplied as a ready-to-use premix in a 5 gallon pack size. The formulation should not be diluted prior to use.
Fernox Solar S1 is classified as non-hazardous, but as with all chemicals, keep out of the reach of children. Refer to the Safety Data Sheet (SDS) for further information.